產(chǎn)品列表 / products
ARM55D-000開關(guān)量端子板日本橫河YOKOGAWA一般規(guī)格書
接線端子板 重量2.6公斤
Mechanical Relay Boards (Contact Output)
1、技術(shù)指標(biāo):
作用形式: 機(jī)械式繼電器隔離輸入
內(nèi)部連接形式:IDC座 50P 兩組 可單一或冗余輸出
輸入信號: ON:≤150Ω;OFF:≥200KΩ
現(xiàn)場連接形式: M3.5螺釘帶透明蓋板端子塊四組,端子塊可整體帶線拔插
內(nèi)部電源供電: 24VDC 0.32A,帶LED指示和過流、過壓、反接保護(hù)
現(xiàn)場電源供電: 雙路(每16點(diǎn)為一路)24VDC,每路大0.3A,帶LED指示和過流、過壓、反接保護(hù)
回路指示: LED動作指示
絕緣電阻:小10MΩ(500VDC)
環(huán)境溫度和濕度: 0~50℃,10~90%RH
安裝尺寸:M5M6螺釘*4 468*51mm(18"*2")
尺寸:482mm*111mm(寬19",2.5U)
重量:1.4Kg
2、配套DCS卡件表:
ADV151 配套電纜: AKB331
ADV161 配套電纜: AKB337
ARM55D-000開關(guān)量端子板日本橫河YOKOGAWA一般規(guī)格書
Models | ARM55D | ARM55W ARM55T (with switch) | ARM55C |
Usage |
Mechanical Relay DryContact Output (“a”contact (NO)) (Single / Dual-redundant) | Mechanical Relay WetContact Output (Single /Dual-redundant) AUTO/OFF/ON switch (onlyfor ARM55T) | Mechanical Relay Dry Contack Output (“a” contact or “b” contact (NO or NC)) (Single / Dual-redun or dant)(*6) |
Contact Points | 32-point | 32-point | 32-point |
Terminals for Field Device Connection |
M4 screws |
M4 screws | M3.5 screws (*5) (M4 in power input part) |
Modules | ADV551 (DO: 32-point) + ATD5A (Terminal block)ADV561 (DO: 64-point)(*1) | ADV551 (DO: 32-point) + ATD5A (Terminal block)ADV561 (DO: 64-point)(*1) | ADV551 (DO: 32-point) + ATD5A (Terminal block)ADV561 (DO: 64-point)(*1) |
Signal Cables | AKB331 (for 32-point)AKB337 (for 64-point) | AKB331 (for 32-point)AKB337 (for 64-point) | AKB331 (for 32-point)AKB337 (for 64-point) |
Maximum Load (*2) | 250 V AC: 2 A per point 30 V DC: 2 A per point 125 V DC: 0.1 A per point (*3) | 250 V AC: 0.6 A per point 30 V DC: 0.6 A per point 125 V DC: 0.1 A per point (*3) |
30 V DC: 1.5 A per point |
Minimum Load | 5 V, 10 mA | 5 V, 10 mA | 5 V, 10 mA |
Power Supply Voltage and Current Consumption of Internal Circuit (requireexternal power supply) |
24 V DC Max.0.65 A |
24 V DC Max.0.65 A |
24 V DC Max.0.85 A |
Power Supply for Field Device (require external powersupply) |
- | Dual-line (supply power per 16-point) 250 V AC: Max. 9.6 A 30 V DC: Max. 9.6 A 125 V DC: Max. 1.6 A |
- |
Insulation Resistance | At least 10 MΩ (500 V DC) | At least 10 MΩ (500 V DC) | At least 10 MΩ (500 V DC) |
Withstanding Voltage | Between ?eld device terminalsand cases: 2 kV Between 24 V power terminals and cases: 500 V Between 24 V power terminals and ?eld device terminals: 2 kV | Between ?eld device terminalsand cases: 2 kV Between 24 V power terminals and cases: 500 V Between 24 V power terminals and ?eld device terminals: 2 kV | Between ?eld device terminalsand cases: 2 kV Between 24 V power terminals and cases: 500 V Between 24 V power terminals and ?eld device terminals: 2 kV |
Ambient Temperature and Humidity |
0 to 50 °C, 10 to 90 %RH |
0 to 50 °C, 10 to 90 %RH |
0 to 50 °C, 10 to 90 %RH |
Standards | Safety Standard [CSA] (*3)EMC standards [CE Marking], [C-Tick Marking], [KC Marking] | Safety Standard [CSA] (*3)EMC standards [CE Marking], [C-Tick Marking], [KC Marking] | EMC standards [CE Marking], [C-Tick Marking], [KC Marking](*4) |
Size | W: 482.6 mm x H: 132.5 mm (3U) | W: 482.6 mm x H: 177 mm (4U) | W: 482.6 mm x H: 132.5 mm (3U) |
Weight |